► EXMEDIIBT4 GRADE ANTI EXPLOSION DESIGN
Flameproof type IVR. Two isolated flame-proof enclosures. The transformer is in the main enclosure with anti-explosion and shake-proof functions.
Another enclosure is used to place control board, display, power switch and the wires.
► HARSH ENVIRONMENTS DESIGN
Compose of high efficiency and wide safety range of industrial grade components, the IVR can sustain severe temperature, humidity, vibration and dirty environments.
► PRECISE & LINEAR VOLTAGE OUTPUT
Output voltage accuracy can be stabilized in a safety working range, even in frequently voltage fluctuation areas.
► ADJUSTABLE OUTPUT VOLTAGE ACCURACY
Output voltage accuracy is adjustable from ±2 % ~ ±10 %, through jumper setting on the regulation board.
► FULL ADVANCED PROTECTION WITH BUZZER ALARM AND INDICATOR FLASHING
The integrated automatic protection circuit offers a full range of protection to protect the IVR and the loads. When output voltage exceeds the upper or lower limit, open phase or phase reversal, the output will be cut off automatically, buzzer alarms and LED indicators are flashing.
► STRONG OVERLOAD CAPABILITY
The IVR will not be damaged when short circuit on the loads or over current in transient. 100 % / continuous, 150 % / 30 seconds, 200 % / 10 seconds, 300 % / 5 seconds.
• Designed to withstand HEAVY loads currents
• Designed to withstand HIGH motor startup/inrush currents
► FULLY ISOLATED MANUAL BYPASS
Through fully-isolated manual bypass switch, the IVR can be connected to mains.
► LONG DELAY POWER CUT PROTECTION
Instantaneous power outage and recovery will damage electrical devices.
The IVR can delay off 3 minutes and boost automatically to ensure the security of load.
► EASY MAINTENANCE AND SERVICE
Complete Modular design for easy and fast maintenance / service.
Standardization Components. Only keeps the outer appearance clean, no extra service and maintenance is required.
► INSTANT POWER SUPPLY PROTECTION
When user wants to have power supply immediately, press "Fast Power" button to have instant power supply, also avoid electrical hazards from high voltage - spike.
► CUSTOMIZATION WELCOME
Listen and design to meet with your demands.
MODEL | HPI-AE | ||
Phase | 1Phase System | 3Phase System | |
Rated Capacity | 5KVA ~ 100KVA | 5KVA ~ 300KVA | |
INPUT | |||
Input Nominal Voltage | 110V System: 110/120/127V 220V System: 220/230/240V |
220V System: 220/230/240/254V 380V System: 380/400/415/440V |
|
Input Voltage Range | ±15% (±20%~±30%, or Customized) | ||
Nominal Frequency | 50Hz or 60Hz | ||
Input Frequency Range | ±5Hz | ||
Input Power Factor | > 98% | ||
Applicable Loads | Resistive, Capacitive, Inductive Loads | ||
OUTPUT | |||
Output Wave Form | Pure Sine Wave | ||
Output Voltage Accuracy | Preset at ±2% (±2%~±10% Adjustable) | ||
Output Harmonic Distortion | <3% | ||
Output Power Factor | 0.8 | ||
Output Efficiency | >96% | ||
Overload Ability | 150% / 30Seconds, 200% / 10Seconds, 300% / 5Seconds | ||
INDICATION | |||
Input Voltage | Analog Voltmeter | ||
Output Voltage | Analog Voltmeter | ||
Output Current | Analog Current Meter | ||
Output On | LED Indicator | ||
Output Off | LED Indicator | ||
Output High Voltage | LED Indicator | ||
Output Low Voltage | LED Indicator | ||
PROTECTION & ALARM | |||
Over Voltage Protection | ≦2 / 4 / 5V Settable | ||
Output High Voltage | Output Cutoff + LED Indicator + Buzzer | ||
Output Low Voltage | Output Cutoff + LED Indicator + Buzzer | ||
Output Phase Failure | Cutoff + Buzzer | ||
Output Overload | Input Circuit Breaker Cutoff | ||
Load Short Circuit | Input Circuit Breaker Cutoff | ||
Manual Bypass | Yes (Option: Automatic Bypass) | ||
Time Delay Off | Long: 3 ~ 7minutes Settable / Short: 3 ~ 7seconds settable | ||
Delay Output | Optional Replaceable Module | ||
SAFETY | |||
Dielectric Strength(Coil to Earth) | 60V~300V:2,000V/60S (20mA) | 300V~660V:2,500V/60S (20mA) | |
Insulation Resistance | ≧5MΩ(Coil to Earth) | ||
Creepage Distance | > 8mm | ||
Grounding Resistance | < 0.1MΩ | ||
Shock Resistance | 0.3G | ||
Temperature Rating of Coil | Class F, 155°C / Class H, 180°C | ||
Cooling Mode | Natural | ||
Anti-explosion Level | According to request by Customer | ||
ENVIRONMET | |||
Audible Noise | < 65dB at 1m distance with full load | ||
Operation Humidity | 0% ~95% (non-condensing) | ||
Operation Temperature | -10°C ~40°C | ||
Operation Altitude | < 1,000m | ||
Storage Temperature | -20°C ~40°C | ||
Remarks: | 1. Different specifications required are available | ||
2. All specifications mentioned above are subject to change without prior notice. |
• SURGE PROTECTION DEVICE
Additional Surge Protection Device can be fitted to suppress surge and spike from mains power.
• RS-232 / RS485 FOR REMOTE MONITORING AND CONTROL
• FREE CONTACT POINTS FOR ABNORMAL SIGNAL
The IVR provides all kinds of abnormal signals (DC5V) for external control.
About Anti-Explosion
CLASSICATION OF HAZARDOUS AREAS | ||
Explosive Gas Atmosphere |
Combustible Dust Atmosphere |
Description |
Zone 0 | Zone 20 | A place in which an explosive atmosphere or dust atmosphere is aroused continuously, or exists for long periods of time |
Zone 1 | Zone 21 | A place in which an explosive atmosphere or dust atmosphere is likely occurred under normal operation |
Zone 2 | Zone 22 | A place in which an explosive atmosphere or dust atmosphere Is impossible occurred under normal operation but, if it does occur, will persist for only a short period |
TEMPERATURE CLASSIFICATION | |
Group | Surface Temperature(℃) |
T1 | 450 |
T2 | 300 |
T3 | 200 |
T4 | 135 |
T5 | 100 |
T6 | 85 |
DEVICE GROUP | |
Group | Typical Gas & Dust |
T1 | All underground coal mining firedamp(methane) |
T2 | Industrial methane, propane, petrol and the majority of industrial gases |
T3 | Ethylene, coke oven gas and Other industrial gases |
T4 | Hydrogen, acetylene, carbon disulphide |
T5 | Combustible flyings |
T6 | Combustible flyings |
TYPE OF PROTECTION | |||
Code | Type of Protection | Application | IEC Standard |
d | Flameproof Enclosure | GAS | IEC60079-1 |
e | Increased Safety | IEC60079-7 | |
o | Oil Field | IEC60079-6 | |
q | Sand / Powder / Quartz Filled | IEC60079-5 | |
p | Pressurized Enclosure | IEC60079-2 | |
i | Intrinsic Safety | IEC60079-25, IEC60079-11, IEC60079-27 | |
n | Non Incentive | IEC60079-15, IEC60079-27 | |
s | Special Protection | IEC60079-33 | |
m | Gas & Dust Encapsulation | Gas & Dust | IEC60079-18 |
m | Gas & Dust Encapsulation | Dust | IEC60079-18 |
tD | Dust-Protection by Enclosure | IEC61241-1 | |
pD | Dust-Pressurization | IEC61241-2, IEC61241-4 | |
iD | Intrinsic Safety | IEC61241-11 |
EQUIPMENT PROTECTION LEVEL (EPL) | ||||
Group | Ex risk | Zone | EPL | Min. Type of Protection |
I (mines) |
Energized | Ma | ||
De-energized in presence of Ex atmosphere | Mb | |||
II (gas) |
Ex-atmosphere > 1000 hrs / yr | 0 | Ga | |
Ex-atmosphere between 10 and 1000 hrs / yr | 1 | Gb | ia, ma | |
Ex-atmosphere between 1 and 10hrs / yr | 2 | Gc | Ib, mb, px, pv, e, o, q, s | |
III (dust) |
Ex-surface > 1000hrs / yr | 20 | Da | n, ic, pz |
Ex-surface between 10 and 1000 hrs / yr | 21 | Db | ||
Ex-surface between 1 and 10h rs / yr | 22 | Dc |