● Home> Products > Power Inverter > 12 / 24 / 48Vdc Telecom Inverter, Rack-mount Type > 24 / 48Vdc Telecom Inverter, Rack-mount Type (3U 5KVA)

24 / 48Vdc Telecom Inverter, Rack-mount Type (3U 5KVA)
• | AC Power for Battery | • | Emergency Lighting |
• | ATS | • | ETC |
• | Automation | • | Medical Equipment |
• | Car Electrification | • | Railway Field |
• | Civil and Military Nautical | • | Telecom System |
Clean,Highly Regulated Power Supply ! | ||
• | For Telecom:12 / 24 / 48Vdc DC Voltage. | |
• | For Power Plant:110 / 220Vdc DC Voltage. | |
• | 1U / 2U / 3U 19" or 23" Rack-mount type. | |
• | 1U / 2U / 3U 19" or 23" Open Frame Cabinet. | |
• | Digital Displays. | |
• | Pure Sine Wave Output (THD <3%) Resistive Load. | |
• | Bypass Function. | |
• | Advanced Microprocessor. | |
• | Inverter mode / UPS mode (Option) | |
• | Built-in Transfer Switch. | |
• | Loading & Temperature Controlled Cooling Fan. | |
• | Output Frequency : 50 / 60Hz Switch. | |
• | Adjustable Output Voltage. | |
• | Reliable Input Surge Protection & EMI Suppression. | |
• | Modularized IGBT infrastructure to ensure better durability. | |
• | Cold start function (DC start) functionality allows unit to operate with battery only. | |
• | RS-232 Interface / Wire Connection to PC. | |
• | Option: SNMP Interface / Dry Contacts / Remote Control. | |
• | Protection : Input Under Voltage, Input Over Voltage, Overload, Short Circuit, | |
Low Battery Alarm, Over Temperature. | ||
• | CUSTOMIZATIONS WELCOME |
3U 19" Rack Mount Type (5KVA) |
Model |
A:110V E: 220V |
SPI-R3- 2405A |
SPI-R3- 4805A |
SPI-R3- 1105A |
SPI-R3- 2205A |
SPI-R3- 2405E |
SPI-R3- 4805E |
SPI-R3- 1105E |
SPI-R3- 2205E |
Outlook | Rack Mount | 19" 3U | |||||||
Capacity | Continuous O/P Power | 5000W | |||||||
Surge Rating | 5200W @ 3 Minutes | ||||||||
Peak | 10000W | ||||||||
DC Input | I/P Voltage | 24Vdc | 48Vdc | 110Vdc | 220Vdc | 24Vdc | 48Vdc | 110Vdc | 220Vdc |
I/P Voltage Range | 20-32Vdc | 42-62Vdc | 90-140Vdc | 180-275Vdc | 20-32Vdc | 42-62Vdc | 90-140Vdc | 180-275Vdc | |
Over Voltage Alarm | 31.0Vdc | 61.0Vdc | 135.0Vdc | 270.0Vdc | 31.0Vdc | 61.0Vdc | 135.0Vdc | 270.0Vdc | |
Over Voltage Cut-off | 32.0Vdc | 62.0Vdc | 140.0Vdc | 275.0Vdc | 32.0Vdc | 62.0Vdc | 140.0Vdc | 275.0Vdc | |
Under Voltage Alarm | 21.0Vdc | 43.0Vdc | 95.0Vdc | 185.0Vdc | 21.0Vdc | 43.0Vdc | 95.0Vdc | 185.0Vdc | |
Under Voltage Cut-off | 20.0Vdc | 42.0Vdc | 90.0Vdc | 180.0Vdc | 20.0Vdc | 42.0Vdc | 90.0Vdc | 180.0Vdc | |
Bypass (AC Input) (Option) |
Nominal Voltage | A: 1 Phase 2W+G, 100Vac -120Vac (Tune VR) | E: 1 Phase 2W+G, 200Vac - 240Vac (Tune VR) | ||||||
Frequency | (50Hz - 60Hz) ± 3% | (50Hz - 60Hz) ± 3% | |||||||
Protection | Electronic Circuits & AC Circuit Breaker | ||||||||
Bypass | Inverter ⇔ Bypass | 4 - 6 ms | |||||||
Inverter⇔Bypas Mode | Inverter Mode or UPS Mode by Switch (Option) | ||||||||
AC Output | AC Voltage Adjustment | A: 1Phase 2W+G, 100 - 120 Vac (Tune VR) | E: 1Phase 2W+G, 200 - 240 Vac (Tune VR) | ||||||
Voltage Accuracy | < 2% at Linear Load | ||||||||
Frequency | 50Hz / 60Hz ± 0.05% (Switch Selectable) | ||||||||
Output Wave Form | Pure Sine Wave, <3% THD @ Resistive Load | ||||||||
Output Power Factor | 1.0 | 1.0 | |||||||
Peak Output Current | 91A | 45A | |||||||
Efficiency @ Full Load | 85% | 87% | 90% | 92% | 90% | 92% | 94% | 94% | |
No Load Current Draw | 1.64A | 0.82A | 0.42A | 0.24A | 1.3A | 0.68A | 0.35A | 0.18A | |
Standby Current Draw | <=1.5W Power Saving Mode | <=1.5W Power Saving Mode | |||||||
Protection | Protection | Overload, Short Circuit, Reverse Polarity (Fuse), Input Under Voltage, Input Over Voltage, Over Temperature |
|||||||
Safety | EN60950-1 | ||||||||
EMC | FCC class A |
EN55022: 2006, Class A EN61000-3 -2: 2006 EN 61000-3-3: 1995+A1:2001+A2-2005 |
|||||||
Indicator | Digital Display | OVP, UVP, OTP, OLP, VAC, AMP, WATT, VDC, TEMP, Hz | |||||||
Communication | Interface Control Unit |
RS-232C with Baud Rate 2400, 4800, 9600, 19200 (Switch Selectable) Option-1: SNMP Interface |
|||||||
Remote Control Unit | Optional | Can't Support | Optional | Can't Support | |||||
Environment | Operating Temperature | -20°C ~ 50°C | |||||||
Storage Temp. Range | -30°C ~ 70°C | ||||||||
Relative Humidity | 0~90%, non-condensing | ||||||||
Cooling | Air Forced Fan | Loading & Temperature Controlled Cooling Fan | |||||||
Mechanical | Dimension | W425 * D504 * H132mm | |||||||
Net Weight | 19.0kgs |
* All specifications mentioned above are subject to change without prior notice.
► | CUSTOMIZATIONS | |
► | HOT STANDBY | |
► | SNMP Interface | |
► | Dry Contacts | |
► | Remote Control |
Introduction |
12 / 24 / 48Vdc 19" or 23" Telecom Inverter, Rack-mount Type is designed for long “MTBF” |
and continue provide manageable and dependable AC power for network demands. |
Featuring an integrated utility bypass function, pure sine wave output and low EMI / RFI emissions, |
SPI-R series Telecom Inverters are well equipped for Telecom and other demanding |
critical applications. |
An intelligent microprocessor-based control and smart software for power management |
include alerts on the LED display interface that ensure safety and reliability. |
A SNMP option is available; and would allow the user remote communication access |
to the inverter. SPI-R Series Power Inverters are among the most reliable systems |
available for electricity and other demanding critical applications. |