Home> Products > AVR / Voltage Stabilizer / Power Line Conditioner > INDUSTRIAL Grade AVR, OUTDOOR > INDUSTRIAL Grade OUTDOOR AVR, Servo Motor Type
INDUSTRIAL Grade OUTDOOR AVR, Servo Motor Type

Model:

SPS-O series

Type:
Servo Motor Type
Capacity:
10~400KVA
Made in
Taiwan
Base Stations Park Electric Equipment
Bridge Perimeter Lighting
Communication Systems Playground Resort
Golf Course Lighting Systems Satellite Operators
Infrastructure Telecom Companies Security Systems
Lighting Systems TV & Radio Broadcasting Stations
Mobile Phone Operators Various United Nations Divisions
Outdoor Electric Equipment   including WHO, UNICEF and WFP
Simple & Reliable AVR You can Trust!
   
IP-54 WEATHER-PROOF ENCLOSURE
 

Designed and manufactured to withstand extremes of high humidity, dry weather

  and dust.
H-GRADE ISOLATION TRANSFORMER (DELTA/WYE) (OPTION)
 

Galvanic isolated is used to protect against electric shock, to suppress electrical

  noise in sensitive devices.
HIGHER LEVEL OF SURGE AND LIGHTNING PROTECTION
 

Special design to deal with high level protection for Telecommunication

  applications and for equipment that require a higher level of Surge, Spike &
  Noise Protection.
BETTER THAN 98 % VA EFFICIENCY, FROM 0 TO 100 % LOAD
  Very low losses and minimal heat dissipation.
SOFT START LOAD PROTECTION
 

Ensure that the output voltage is at its minimum upon Switch-On

  before it commences full stabilization.
INDEPENDENT PHASE CONTROL
 

When AC power encounters phase unbalanced, non-linear power or

  heavy load, each phase keeps maintain its accurate Output voltage.
STRONG OVERLOAD CAPABILITY
  Sustained 200 % of its rated loading capacity, no voltage goes down extremely.
-30 % / +25 % WIDE INPUT VOLTAGE RANGE
  More Wider Input Voltage Range is available on request.
±1% ~ ±2% PRECISE & LINEAR VOLTAGE REGULATION RATE
 

Output Voltage Accuracy can be stabilized within a safety working range,

  even in high voltage fluctuation areas.
FRONT ACCESS CABINET WITH LOCKABLE DOORS
  Easy installation and maintenance.
FULL PROTECTION
  Over Voltage Protection:
   

If Input voltage exceeds voltage regulation range, the AVR will cut off output

    voltage automatically and shield abnormal voltage enters into the AVR directly
    or burn circuit boards.
  Under Voltage Protection:
   

When Input voltage is too low, it will cause malfunctions of machinery automation;

    Product failure rate will increase as well.
  Phase Failure Protection:
   

Should one of the electric wires is disconnected abruptly while AVR is working,

    the AVR will cut off at once and Red light indicator is flashing. Verify if the
    connected equipment remains in Safety Electrical mode and prevent the load
    from serious damage.
  Time Delay-off & Soft Start Protection:
    Instantaneous power blackouts and recovery will damage electrical loads.
    While AC power recovery, the AVR starts automatically from low voltage output,
   

to ensure the security of load.

BYPASS CONTROL SWITCH
VOLTMETER / SELECTOR SWITCH
MANUAL MAINTENANCE BYPASS SWITCH
  The switch is for periodically maintenance and service. Not affect machinery
 

running in any ways.

ABNORMAL LED INDICATORS
  LED displays provide immediate, exact fault states for easier and efficient maintenance.
CONCEALED NON-FUSE CIRCUIT BREAKER
  Prevent man-made damage or careless machine shutdown. Fitted with Overload protection.
SAFETY HIDING-STYLE SWITCH SHIELD
  Prevent damage or man-made wrong action during transportation which would
 

cause no voltage output.

COMPLIANCE WITH INTERNATIONAL STANDARDS
  Electro-Magnetic Compatibility (EMC) Directive: IEC61000-4-2 / 3 / 4 / 5 / 6 / 8 / 11,
  Low Voltage Directive (Safety): EN61000-6-2 / 4
CE CONFORMITY
  European Union Directives 2004/108/EC (The EMC Directive) and
  2006/95/EC (The Low Voltage Directive)
CUSTOMIZATION WELCOME
 

Please contact us, we will welcome the opportunity to review your problems and

  provide you with necessary solutions.




 

TECHNICAL SPECIFICATION (SINGLE PHASE) :

Model No SPS-O-1105 SPS-O-1107 SPS-O-1110 SPS-O-1115 SPS-O-1120 SPS-O-1130 SPS-O-1135 SPS-O-1140
Capacity (KVA) 5 7.5 10 15 20 30 35 40
Input Voltage 230V (Other Voltage on request)
Input Voltage Range   -30% / +25% (Other Voltage Range on request)
Output Voltage 230V (Other voltage on request)
Output Voltage Accuracy ±1% ~ ±5% adjustable (Preset at ±1.5%)
Frequency 47Hz ~63Hz
Power Factor Any lagging to 0.95 leading
VA Efficiency >/= 98% (AC to AC), from 0 to 100 % load
Surge Ratings 10X max current rating for 2 seconds
3X max current rating for 1 minutes
2X max current rating for 5 minutes
Surge Suppression   Protect loads against high-energy spikes and transient voltage
Surge Arrester    40KA at 230V AC Class III (IEC 61643-1:1998-02, EN61643-11:2001)
Distortion   T.H.D. (Total Harmonic Distortion) <1% adds
Response Time <0.1 Second
Correction Time 10 % supply variation will be corrected to within 2.5 % in 0.6 seconds
Overload Capacity 150 % for 10 seconds; 200 % for 2 seconds
Standard Features Input Circuit Breaker
Output Magnetic Contactor
Over / Under Voltage Protection
Overload Protection, Short Circuit Protection
Bypass Control Switch
Voltmeter / Selector Switch
Manual Bypas The switch is for periodically maintenance and service.
Not affect machinery running in any ways
Soft Star To ensure the security of load, the AVR always starts from low voltage
before it commences full stabilization
Construction IP-44: Galvanized sheet, powder coating plus anticorrosive epoxy primer, BS EN5490 / IEC60529 (options: IP-43 / 54 / 66 / 67 / Stainless or others on request)
Conformance BS EN50081-1;2 / IEC 61000-4-3;4
CE Conformit EN55022, EN50082-2, ENV50140-1
Optional Accessories Ammeter/selector switch, Frequency meter
Working Environment 0°C ~ 45°C; 0% ~ 95% (non-condensing)
The cubicle size varies with the input voltage range.
Optional accessories added may affect dimension, subject to confirmation.
We reserve the right to change specifications without prior notice.


  TECHNICAL SPECIFICATION (THREE PHASE) :

Model No.

SPS-O

3310

SPS-O

3315

SPS-O

3320

SPS-O

3330

SPS-O

3345

SPS-O

3360

SPS-O

3375

SPS-O

33100

SPS-O

33120

SPS-O

33150

SPS-O

33200

SPS-O

33250

SPS-O

33300

Capacity (KVA) 10 15 20 30 45 60 75 100 120 150 200 250 300
Input Voltage Range    400/230V,  -30% / +25% (Other voltages on request)
Output Voltage Accuracy  

400/230V, ±1% ~ ±5% adjustable (Preset at ±1.5%) (Other voltage on request)

Frequency   47Hz ~ 63Hz
Power Factor  0.95 ~ 1
VA Efficiency >/= 98 % (AC to AC), from 0 to 100% load
Surge Ratings

10X max current rating for 2 seconds

3X max current rating for 1 minutes

2X max current rating for 5 minutes

Surge Suppression    Protect loads against high-energy spikes and transient voltage
Surge Arrester 40KA at 415V AC Class III (IEC 61643-1:1998-02, EN61643-11:2001)
Distortion T.H.D. (Total Harmonic Distortion) <1% adds
Response Time <0.1 Second
Correction Time A 10% supply variation will be corrected to within 2.5% in 0.6 seconds
Overload Capacity 150% for 10 seconds; 200% for 2 seconds
Phase Unbalance Capable to correct balance within 2% under 30% phase unbalance state
Protection

Input Circuit Breaker, Output Magnetic Contactor, Over/Under Voltage Protection

Overload Protection, Short Circuit Protection, Phase Failure Protection

Bypass Control Switch

Voltmeter / Phase Selector Switch

Manual Bypass

The switch is for periodically maintenance and service. Not affect machinery running in any ways

Soft Start 

Ensure that the output voltage is at its minimum upon Switch-On before it commence full stabilization

Construction

IP-44: Galvanized sheet, powder coating plus anticorrosive epoxy primer, BS EN5490 / IEC 60529
(options: IP-43 / 54 / 66 / 67 / Stainless or others on request)

EMC Conformance BS EN50081-1;2 / IEC 61000-4-3;4
CE Conformity EN55022, EN50082-2, ENV50140-1
Optional Accessories Ammeter / selector switch, Frequency meter
Working Environment 0°C ~ 45°C; 0% ~ 95% (non-condensing)
The cubicle size varies with the input voltage range.
Optional accessories added may affect dimension, subject to confirmation.
We reserve the right to change specifications without prior notice.

        

AUTO RESTORE WHILE AC RECOVERY
 

The system to be automatically switched into operation when power is restored (automatically) during a power failure.

H-GRADE ISOLATION TRANSFORMER (DELTA/WYE)
 

Galvanic isolated is used to protect against electric shock, to suppress electrical noise in sensitive devices.

SPD (Surge Protective Device) or
  TVSS (Transient Voltage Suppressors) Protection

Lightning Protector

Outdoor Enclosure
Optional Accessories:
  Output Circuit Breaker
  Ammeter / Selector Switch
  Frequency Meter

IP DEGREES IN ACCORDANCE WITH IEC 529

 
The Degree of Protection against
The Ingress of Solid Foreign Objects
The Degree of Protection against
The Ingress of Water with Harmful Effects

1st

Digit

Object Size
Protected Against
Effective Against

2nd

Digit

Protected

Against

Testing for
0 Non-protected No special Protection 0 Non-protected No Protection
1

>/= 50 mm

Any large surface of the body,

such  as  the back of a hand,

but no protection against deliberate

contact with a body part

1

Dripping Water

Dripping water

(vertically falling drops)

shall have no harmful effect

2

>/= 12.5 mm

Fingers or similar objects 2

Dripping Water
when tilted up to 15°

Vertically dripping water shall have no harmful

effect when the enclosure is tilted at an angle

up to 15° from its normal position

3

>/= 2.5 mm

Tools, thick wires, etc. 3

Spraying Water

Water falling as a spray

at any angle up to 60°

from the vertical shall

have no harmful effect

4

>/= 1mm

Most wires, screws, etc. 4

Splashing Water

Water splashing against the enclosure from

any direction shall have no harmful effect.

5

Dust

protected

Ingress of dust is not entirely prevented,

but it must not enter in sufficient quantity to

interfere with the satisfactory operation of the

equipment, complete protection against contact

5

Water Jets


Water projected by a nozzle (6.3mm)

against enclosure from

any direction shall have

no harmful effects

6

Dust-tight

No ingress of dust,

complete protection

against contact

6

Powerful

Water Jets

Water projected in powerful jets

(12.5mm nozzle)

against the enclosure from

any direction shall have no harmful effects

 For example, IP20 means:
  2  -  Protected against solid foreign objects

          of >/= 12.5 mm dia
  0 -   Non-protected against the ingress of

          water with harmful effects

 

7

Temporary

Immersion up to 1m

Ingress of water in

harmful quantity shall

not be possible when

the enclosure and time

(up to 1m of submersion)

8

Immersion

Beyond 1m

The equipment is suitable

for continuous immersion

in water under conditions

which shall be specified

by maker